MD320 Frequency Converter |
Power Capacity (kVA): 1~630
Input Current (A): 5.4~883
Output Current (A): 2.3~820
Appropriate Motor (kW): 0.4~450
Technical parameters
Item |
Specifications |
||
---|---|---|---|
Individualized function
|
maximum frequency
|
300Hz |
|
Carrier frequency
|
0.5k to 16kHz; the carrier frequency will be automatically adjusted according to the load characteristics. |
||
Input frequency resolution
|
Digital setting: 0.01Hz Analog setting: maximum frequency ×0.1% |
||
Control mode
|
Open loop vector control (SVC) Close loop vector control (VC) V/F control |
||
Startup torque
|
G model: 0.5Hz/150% (SVC); Hz/180%(VC) P model: 0.5Hz/100% |
||
Speed adjustment range
|
1:100 (SVC) |
1:1000 (VC) |
|
Speed stabilization precision
|
±0.5%(SVC) |
±0.02%(VC) |
|
Torque control precision
|
±5%(VC) |
||
Overload capacity
|
G model: 150% rated current 60s; 180% rated current 1s. P model: 120% rated current 60s; 150% rated current 1s. |
||
Torque hoist
|
Automatic torque hoist; manual torque hoist 0.1% to 30.0% |
||
V/F curve
|
Three types: straight line, multiple point and square type |
||
Speed-up and Speed-down curve
|
Straight line or S curve speed-up and speed-down mode; four kinds
of speed-up and speed-down time; speed-up and speed-down time ranges
between 0.0s to 3000.0s. |
||
DC brake
|
DC brake frequency: 0.00Hz to maximum frequency; brake time: 0.0s to 36.0s, and brake current value: 0.0% to 100.0%. |
||
Jog control
|
Jog frequency range: 0.00Hz to 50.00Hz; jog acceleration/deceleration time: 0.0s to 3000.0s. |
||
Simple PLC and MS Speed Running
|
It can realize a maximum of 16 segments speed running via the built-in PLC or control terminal. |
||
Built-in PID
|
It is easy to realize process-controlled close loop control system. |
||
Auto voltage regulation (AVR)
|
It can keep constant output voltage automatically in case of change of mains voltage. |
||
Torque limit and control
|
It can limit the torque automatically and prevent frequent over
current tripping during the running process; the close loop vector mode
can implement torque control. |
||
Individualized function
|
Peripherals self-detection upon power-on
|
It can conduct safety detections on the peripherals upon power-on, including earth and short circuit detections. |
|
Shared DC Bus Function
|
It can realize the function that multiple inverters share the DC bus. |
||
QUICK key
|
The user can freely define short-cut menus. |
||
MF.K Key
|
Programmable key: Select the command channel switching/forward and reverse rotations/jog operation. |
||
Textile swing frequency control
|
Multiple triangular-wave frequency control function |
||
Length control
|
Reference length control function |
||
Timing control
|
Timing control function: Setting time range between 0h to 65535 h. |
||
Run
|
Running command channel
|
Three types of channels: operation panel reference, control
terminal reference and serial communication port reference. These
channels can be switched in various modes. |
|
Frequency source
|
There are totally ten types of frequency sources, such as digital
reference, analog voltage reference, analog current reference, pulse
reference and serial port reference. These frequency sources can be
switched in various modes. |
||
Auxiliary Frequency source
|
There are ten types of auxiliary frequency sources. It can implement micro tuning and synthesis of auxiliary frequency. |
||
Input terminal
|
There are five digital input terminals, one of which can be used as
high-speed pulse input. (The number of digital input terminals can be
expanded to ten) It can be compatible with active PNP or NPN input mode. There are two analog input terminals, one of which can be used only as voltage input, while the other can be used as voltage or current input. (It can expand one voltage input terminal) |
||
Output terminal
|
There is one high-speed pulse output terminal (can be
selected as open collector mode), with square wave output of 0kHz to
50kHz. It can output such physical parameters as setting frequency and
output frequency. One digital output terminal (can be expanded to two) One relay output terminal (can be expanded to two) One analog output terminal (can be expanded to two), with optional 0//4mA to 20mA or 0/2V to 10V. It can realize the output of such physical parameters as setting frequency and output frequency. |
||
Display and Keyboard Operation
|
LED display
|
It can display the parameters |
|
LED display
|
It is an optional part, and can display operation contents Chinese/English. |
||
parameter copy
|
It enables the parameter copy unit to copy the parameters quickly. |
||
Key locking and function selection
|
It can lock the keys partially or completely and define the
functional range of certain keys so as to prevent error operations. |
||
protection function
|
It can implement power-on motor short-circuit detection,
input/output phase loss protection, over current protection, over
voltage protection, under voltage protection, over heat protection and
overload protection. |
||
Optional parts
|
LCD operation panel, multifunctional I/O expansion card, braking
components, communication card, extension card, PG card, water supply
card, etc. |
||
Environment
|
Using Place
|
Indoor, and be free from direct sunlight, dust, corrosive gas, combustible gas, oil smoke, vapor, drip or salt. |
|
Altitude
|
Lower than 1,000 meters |
||
ambient temperature
|
-10 ℃Celsius to +40 ℃Celsius (derated when used in the ambient temperature of 40 ℃ Celsius to 50 ℃ Celsius) |
||
Humidity
|
Less than 95%RH, without condensing |
||
Vibration
|
Less than 5.9 m/s2(0.6g) |
||
Storage temperature
|
-20 Celsius to +60 Celsius |
MD320Inverter Series
Inverter model
|
Power capacity
(kVA)
|
Input current
(A)
|
Output current
(A)
|
Adaptable Motor
(kW)
|
|
---|---|---|---|---|---|
Single-phase Power supply:200…240V,50/60Hz
|
|||||
MD320NS0.4
|
1.0
|
5.4
|
2.3
|
0.4
|
0.5
|
MD320NS0.7
|
1.5
|
8.2
|
4.0
|
0.75
|
1
|
MD320NS1.5
|
3.0
|
14.0
|
7.0
|
1.5
|
2
|
MD320NS2.2
|
4.0
|
23.0
|
9.6
|
2.2
|
3
|
Inovance - Leading Frequency Inverter,Frequency Converter Drive Manufacture in China
0 comments:
Post a Comment